The GSHP-C Series provides commercial and industrial thermal management by utilizing shallow geothermal loops (soil, groundwater, or surface water) as a stable thermal reservoir. This architecture isolates thermal efficiency from ambient air temperature fluctuations across demanding climates.
Configurations: Monoblock indoor installation or split system.
Capacity Range: 30 kW to 520 kW per single unit; modular parallel expansion up to 2.6 MW.
Compliance: AHRI 600/1320 rating methodology, CE certified (LVD, PED), ISO 9001 manufactured.
Key Features
Closed and Open Loop Compatibility: Engineered for vertical U-tube borehole fields, horizontal trench loops, and open-source water extraction with corrosion-resistant metallurgy.
Dual-Circuit Redundancy: Units exceeding 100 kW utilize dual independent refrigeration circuits with tandem compressors, maintaining partial operation during maintenance.
Acoustic Isolation: Galvanized steel panels lined with 50mm high-density acoustic fiberglass wool and hermetic compressor blankets, restricting sound pressure levels below 65 dB(A) at 1 meter.
BMS Integration: Native support for BACnet MS/TP, Modbus RTU, and Modbus TCP/IP protocols.
Technical Specifications
|
Technical Parameter |
Unit |
GSHP-C-060 |
GSHP-C-120 |
GSHP-C-240 |
GSHP-C-360 |
|
Nominal Cooling Capacity |
KW |
62.5 |
125.0 |
242.0 |
365.0 |
|
Nominal Heating Capacity |
KW |
68.0 |
136.0 |
260.0 |
390.0 |
|
Cooling Power Input |
KW |
12.2 |
23.8 |
46.5 |
69.2 |
|
Heating Power Input |
KW |
14.1 |
27.2 |
52.8 |
78.5 |
|
EER (Energy Efficiency Ratio) |
W/W |
5.12 |
5.25 |
5.20 |
5.27 |
|
COP (Ground Loop: 0 deg C / Water: 35 deg C) |
W/W |
4.82 |
4.98 |
4.92 |
4.96 |
|
Compressor Type |
- |
Hermetic Scroll (1x) |
Hermetic Scroll (2x) |
Semi-Hermetic Screw (2x) |
Semi-Hermetic Screw (2x) |
|
Refrigerant Circuit Count |
- |
1 |
2 |
2 |
2 |
|
Source Side Water Flow Rate |
M3/h |
13.5 |
27.0 |
52.5 |
79.0 |
|
Load Side Water Flow Rate |
M3/h |
11.8 |
23.5 |
45.8 |
68.5 |
|
Max. Working Pressure (Water Side) |
MPa |
1.6 (Option: 2.5 MPa) |
1.6 (Option: 2.5 MPa) |
2.5 |
2.5 |
|
Power Supply |
V/Ph/Hz |
380-415V/3Ph/50Hz (460V/60Hz Optional) |
|||
|
Sound Pressure Level (1m) |
DB(A) |
58 |
61 |
64 |
66 |
|
Unit Dimensions (L x W x H) |
Mm |
1450 x 850 x 1650 |
2100 x 900 x 1750 |
2800 x 1100 x 1850 |
3200 x 1200 x 1850 |
|
Operating Weight |
Kg |
580 |
950 |
1720 |
2350 |
Technology and Performance
Heat Exchanger Metallurgy
Source Side: 316L stainless steel brazed plate heat exchangers. Titanium (Grade 1) shell-and-tube or plate evaporators applied for open-loop or high-salinity water installations to prevent chloride stress corrosion.
Load Side: Shell-and-tube condensers featuring seamless inner-grooved copper tubes expanded into carbon steel tube sheets (compatible with up to 40 percent glycol-water concentration).
Operating Envelope
Source-Side Entering Water Temperature (EWT): -5 deg C to 35 deg C.
Load-Side Leaving Water Temperature (LWT):
Cooling: 5 deg C to 20 deg C
Heating: 35 deg C to 55 deg C
Control Logic
Electronic Expansion Valves (EEV) controlled by high-speed stepper motors (500 steps precision) regulate superheat under partial load fluctuations.
Microprocessor controllers monitor approach temperatures for freeze protection and automatic compressor run-hour balancing.
Applications
Commercial Office Complexes: Simultaneous multi-zone heating and cooling via multi-pipe or variable water volume loops.
District Ambient Energy Networks: Centralized mechanical plants serving multi-building low-temperature distribution grids.
Institutional Facilities: Educational and healthcare installations requiring quiet operation and precise zone control.
Industrial Process Cooling: Data centers and manufacturing plants requiring continuous baseline thermal control.
OEM and ODM Customization
Hydraulic Modules: Factory integration of variable-speed circulation pumps, expansion vessels, buffer tanks, and strainers inside the chassis.
Alternative Refrigerants: Circuit adaptation for low-GWP media (R32, R290) complying with ASHRAE 34 and EN 378 safety limits.
Electrical Frameworks: Regional control architectures, UL/CSA-listed components, and dual-power Automatic Transfer Switches (ATS).
Private Labeling: Custom powder coating (RAL color matching), laser-etched stainless steel nameplates, and customized documentation.
Quality Control and Testing
Pressure Testing: Nitrogen holding tests at 3.0 MPa for 24 hours on all refrigerant circuits.
Leak Detection: 100 percent helium mass spectrometer tracer gas testing on all brazed joints (detecting leak rates below 1x10^-7 Pa*m3/s).
Electrical Safety Validation: Dielectric strength testing at 1800V/1s and insulation verification exceeding 100 Mohm at 1000V DC.
Run-Test Validation: Automated dynamometer test benches evaluate thermal capacity, power input, and flow verification under simulated geographic operating profiles.
Packaging and Shipping
Structural Skid: Bolted to heavy-duty structural steel fumigation-free wooden skids using grade-8 zinc-plated hardware.
Moisture Protection: Wrapped in heavy-duty polyethylene film with industrial silica gel desiccant packs sealed inside control cabinets and compressor compartments.
External Armor: Reinforced plywood crating with marked forklift pockets and overhead crane lifting lugs indicating center-of-gravity.
Logistics Support: Containerized loading (20ft / 40ft High Cube) or flat-rack transport with bills of lading, packing lists, and certificates of origin.
FAQ
Request a Quote
Provide the following project parameters for a formal technical proposal and commercial quotation:
Project Location & Climate Data: (Design ambient temperatures, ground thermal conductivity)
Required Capacities: (Peak cooling and heating loads in kW or tons)
Hydraulic Parameters: (Source-side and load-side entering/leaving water temperatures)
Electrical Specification: (Local voltage, phase, and frequency)
Configuration Requirements: (Monoblock/split, pump integration, specific certifications)
Hot Tags: ground source heat pump, China ground source heat pump manufacturers, suppliers, factory, consistent heating and cooling heat pump, dependable heating and cooling heat pump, emergency heating and cooling heat pump, holistic approach heating and cooling heat pump, indoor heating and cooling heat pump, portable heating and cooling heat pump